2 l_ioparalnmodule - parameterisation function, L_ioparalnmodule − parameterisation function, Function library lenzeiosystem.lib – Lenze DDS Function library IOSystem User Manual

Page 22: 2 l_ioparalnmodule − parameterisation function, Function blocks

Advertising
background image

4.2

L_IOParAlnModule − Parameterisation function

Function library LenzeIOSystem.lib

Function blocks

4−4

L

LenzeIOSystem.lib EN 1.7

4.2

L_IOParAlnModule − Parameterisation function

By means of the L_IOParAInModule function block, the analog input modules (EPM−T310 / 311 /
T312) are parameterised. Parameterisation is started by a high edge on the input

bExecute.

Each module has four channels, whereby each channel can be set individually.

The following is provided:

·

Voltage measurement

·

Current measurement

·

Resistance measurement

·

Temperature measurement

On the output of the function block, the transmission status and the information on the connected
modules are displayed.

BEnableDiagnosticAlarm *

bEnableAnalogInterrupt

BySampleRate_CH1 *

L_IOParAInModule

bExecute

byNodeAdr

nState

CTRL

byAnalogModuleNo

byFunctionInput_CH1

ByTriggerSelection_CH1 *

byFunctionInput_CH4

BySampleRate_CH4 *

BySelectionFcn_CH4 *

BySelectionFcn_CH1 *

ByTriggerSelection_CH4 *

ByTriggerValue_CH4 *

ByHysteresis_CH1 *

ByHysteresis_CH4 *

ByTriggerValue_CH1 *

EPM-T110

Ixxxh

EPM-T111

*

Input/function is exclusively supported by type EPM−T310.