Function library LenzeIOSystem.lib
Appendix
6.2
Signal functions for analog outputs EPM−T320
6−5
L
LenzeIOSystem.lib EN 1.7
Parameter
bytes 2/3/4/5
Tolerance
1)
Signal
resolution
Signal range
Signal function
0B
h
Current signal output
(complement on two)
±20 mA
−20.00
−27648
{0.01 mA}
{1 dec}
+20.00
27648
A
±0.05 %
Lower range limit:
−23.70 mA
−32767 dec
Upper range limit:
+23.70 mA
+32767 dec
0C
h
Current signal output
(complement on two)
4 ... 20 mA
4.00
0
{0.01 mA}
{1 dec}
20.00
27648
A
±0.05 %
Lower range limit:
0 mA
−5530 dec
Upper range limit:
+22.96 mA
+32767 dec
0E
h
Current signal output
(complement on two)
0 ... 20 mA
0
0
{0.01 mA}
{1 dec}
20.00
27648
A
±0.2 %
Lower range limit:
–
Upper range limit:
+22.96 mA
+32767 dec
1)