Function library lenzeiosystem.lib, Appendix, Input range (channels 0, 1) – Lenze DDS Function library IOSystem User Manual

Page 76

Advertising
background image

6.3

Signal functions for analog inputs and outputs EPM−T330

Function library LenzeIOSystem.lib

Appendix

6−6

L

LenzeIOSystem.lib EN 1.7

6.3

Signal functions for analog inputs and outputs EPM−T330

Input range (channels 0, 1)

Parameter
bytes 2/3/4/5

Signal function

Signal range

Format

Tolerance

1)

00

h

Parameter data in module not overwritten

3B

h

Voltage measuring
(complement on two)

±10 V

−10.00
−16384

{0.01 V}

{1 dec}

+10.00

+16384

B

±0.2 % of limit value

Lower range limit:

−12.50 V

−20480

dec

Upper range limit:

+12.50 V

+20480

dec

75

h

Voltage measuring

0...10 V

0.00
0

{0.01 V}

{1 dec}

+10.00

+16384

B

±0.4 % of limit value

Lower range limit:

Upper range limit:

+12.50 V

+20480

dec

28

h

Voltage measuring
(complement on two)

±10 V

−10.00
−27648

{0.01 V}

{1 dec}

+10.00

+27648

A

±0.2 % of limit value

Lower range limit:

−11.76 V

−32512

dec

Upper range limit:

+11.76 V

+32511

dec

7A

h

Voltage measuring

1 ... 5V

+1.00
0

{0.01 V}

{1 dec}

+5.00

+27648

A

±0.6 % of limit value

Lower range limit:

0.00 V

−6912

dec

Upper range limit:

+5.704 V

+32511

dec

7D

h

Voltage measuring

0...10 V

0.00
0

{0.01 V}

{1 dec}

+10.00

+27648

A

±0.4 % of limit value

Lower range limit:

Upper range limit:

+11.76 V

+32511

dec

3A

h

Current measuring
(complement on two)

±20 mA

−20.00
−16384

{0.01 mA}

{1 dec}

+20.00

+16384

B

±0.3 % of limit value

Lower range limit:

−25.00 mA

−20480

dec

Upper range limit:

+25.00 mA

+20480

dec

76

h

Current measuring

0 ... 20 mA

0.00
0

{0.01 mA}

{1 dec}

+20.00

+16384

B

±0.6 % of limit value

Lower range limit:

Upper range limit:

+25.00 mA

+20480

dec

2C

h

Current measuring
(complement on two)

±20 mA

−20.00
−27648

{0.01 mA}

{1 dec}

+20.00

+27648

A

±0.3 % of limit value

Lower range limit:

−23.51 mA

−32512

dec

Upper range limit:

+23.51 mA

+32511

dec

2D

h

Current measuring
(complement on two)

4 ... 20 mA

+4.00
0

{0.01 mA}

{1 dec}

+20.00

+27648

A

±0.8 % of limit value

Lower range limit:

+1.18 mA

−4864

dec

Upper range limit:

+22.81 mA

+32511

dec

Advertising