4.3

L_IOParAOutModule − Parameterisation function

Function library LenzeIOSystem.lib

Function blocks

4−8

L

LenzeIOSystem.lib EN 1.7

Outputs

ð

(Variable type: VAR_OUTPUT)

Identifiers

Data type

Value/meaning

nState

Integer

States
If a transmission error occurs during the parameterisation process or the input data
are incorrect, the parameterisation process is aborted and an error number is
indicated at output nState.
Errors are reset via an edge reversal at input bExecute or on
program restart.

0 Transmit request is executed.

The module is parameterised.

1 Transmit request dropped

Processing is running

2001 Error occurred during bus transfer

2002 Transmit request timed out

2004 Access denied

Incorrect target system: subindex does not exist

2005 Access denied

Incorrect target system: index does not exist

2013 Access denied

Incorrect target system: invalid value range

2111 Access denied

Incorrect target system: more than 4 decimal positions
specified or no fixed point format index

2117 Communication channel does not exist

byCom−Channelsetting

−10xx Incorrect value at function block input.

XX := number of faulty input (counting direction down),
parameterisation impossible.
Remedy: change input variable, restart data transmission

Advertising