Function library lenzeiosystem.lib, Appendix, 1 signal functions for analog inputs epm−t310 – Lenze DDS Function library IOSystem User Manual

Page 73

Advertising
background image

Function library LenzeIOSystem.lib

Appendix

6.1

Signal functions for analog inputs EPM−T310

6−3

L

LenzeIOSystem.lib EN 1.7

Parameter
bytes 2/3/4/5

Tolerance

1)

Format

Signal range

Signal function

3A

h

Current measuring
(complement on two)

±20 mA

−20.00
−16384

{0.01 mA}

{1 dec}

+20.00

16384

A

±0.05 % of limit value

Lower range limit:

−23.70 mA

−19456 dec

Upper range limit:

+23.70 mA

+19456 dec

3B

h

Voltage measuring
(complement on two)

±10 V

−10.00
−16384

{0.01 V}

{1 dec}

+10.00

16384

B

±0.2 % of limit value

Lower range limit:

−12.5 V

−20480 dec

Upper range limit:

+12.5 V

20480 dec

3D5

h

Resistance measuring with
four−wire connection

at 60

W

0
0

{0.01

W}

{1 dec}

+60.00

6000 dec

A

±0.1 % of limit value

3E

h

at 600

W

0
0

{0.01

W}

{1 dec}

+600.00

6000 dec

±0.05 % of limit value

3F

h

at 3000

W

0
0

{0.01

W}

{1 dec}

+3000.00

30000 dec

±0.05 % of limit value

57

h

Voltage measuring

0 ... 50 mV

0
0

{0.01 mV}

{1 dec}

+50.00

5000

A

±0.1 % of limit value

Upper range limit:

+59.25 V

5925 dec

58

h

Voltage measuring
(complement on two)

±10 V

−10.00
−10000

{0.01 V}

{1 dec}

+10.00

10000

A

±0.05 % of limit value

Lower range limit:

−11.85 V

−11850 dec

Upper range limit:

+11.85 V

11850 dec

59

h

Voltage measuring
(complement on two)

±4 V

−4.00
−40000

{0.01 V}

{1 dec}

+4.00 V

40000

A

±0.05 % of limit value

Lower range limit:

−4.74 V

−47400 dec

Upper range limit:

+4.74 V

47400 dec

5A

h

Voltage measuring
(complement on two)

±400 mV

−400
−40000

{1 mV}

{1 dec}

+400

40000

A

±0.1 % of limit value

Lower range limit:

−474 mV

−47400 dec

Upper range limit:

+474 mV

47400 dec

5C

h

Current measuring
(complement on two)

±20 mA

−20.00
−20000

{0.01 mA}

{1 dec}

+20.00

20000

A

±0.05 % of limit value

Lower range limit:

−23.70 mA

−23700 dec

Upper range limit:

+23.70 mA

+23700 dec

5D

h

Current measuring
(complement on two)

4 ... 20 mA

4.00
0

{0.01 mA}

{1 dec}

20.00

16000

A

±0.05 % of limit value

Lower range limit:

1.185 mA

−2815 dec

Upper range limit:

+22.96 mA

+22960 dec

FF

h

Analog input deactivated

1)

The tolerance values were established at 25 °C ambient temperature and 15 conversions/s. No sensor inaccuracies were taken into
consideration.

2)

Contact and line resistances were not taken into consideration.

3)

Reference junction compensation to be effected externally.

4)

Reference junction compensation is effected internally, taking into consideration the terminal temperature. Connect the thermocouple
conductors directly to the terminal using a thermocouple extension cable if necessary.