12 l_scb_putnodedatatxpdo2 - data transmission, Plc designer v2.x| lenze application samples – Lenze PLC Designer V2.x User Manual
Page 293

1.3 EN - 07/2012
L
293
PLC Designer V2.x| Lenze Application Samples
The L_SCB_CANBasic.lib library
L_SCB_PutNodeDataTxPDO2 - data transmission
17.12
L_SCB_PutNodeDataTxPDO2 - data transmission
This FB transmits the data via PDO 2.
Inputs
Outputs
Note!
To be able to use the L_SCB_GetNodeDataRxPDO1/
L_SCB_GetNodeDataRxPDO2 FBs in a program, the L_SCB_CanStatus FB must
also be inserted.
• Otherwise, communication to the controller is not possible!
Identifier/data type
Information/possible settings
byNodeNumber
BYTE
Node number
byMasterNumber
BYTE
Interface number (0...3)
awSendData
ARRAY[0..3] OF WORD
Data
Identifier/data type
Information/possible settings
xError
BOOL
"Error" status signal
• Error when reading the data of PDO2
FALSE No error detected
TRUE Error when reading the data