A.6 optional digital inputs, A.7 optional analog outputs, A.8 communication ports – SATEC PM130 PLUS Manual User Manual

Page 136

Advertising
background image

‎Appendix A Technical Specifications

136

PM130 PLUS Powermeter Series

Release time: 0.25 ms max.

Update time: 1 cycle

Connector type: removable, 4 pins.

Wire size: 14 AWG (up to 1.5 mm2)

A.6

Optional Digital Inputs

4 Digital Inputs Dry Contacts, internally wetted @ 24VDC (DI/DO Optional
module)

Sensitivity: Open @ input resistance >100 k

, Closed @ Input

resistance < 100

Galvanic isolation: 3750 VAC 1 min

Internal power supply: 24VDC

Scan time: 1 ms

Connector type: removable, 5 pins.

Wire size: 14 AWG (up to 1.5 mm2)

A.7

Optional Analog Outputs

4 Analog Outputs optically isolated (AO Optional module)

Ranges (upon order):

1 mA, maximum load 5 k

(100% overload)

0-20 mA, maximum load 510

4-20 mA, maximum load 510

0-1 mA, maximum load 5 k

(100% overload)

Isolation: 2500 VAC 1 min

Power supply: internal

Accuracy: 0.5% FS

Update time: 1 cycle

Connector type: removable, 5 pins.

Wire size: 14 AWG (up to 1.5 mm2)

A.8

Communication Ports

COM1

RS-485 optically isolated port

Isolation: 3000 VAC 1 min

Baud rate: up to 115.2 kbps.

Supported protocols: Modbus RTU, DNP3, and SATEC ASCII.

Connector type: removable, 3 pins.

Wire size: up to 14 AWG (up to 1.5 mm2).

COM2 (Optional module)

Ethernet Port

Transformer-isolated 10/100BaseT Ethernet port.

Supported protocols: Modbus/TCP (Port 502), DNP3/TCP (Port 20000).

Advertising