Configuring alarm/control setpoints, Configuring, Alarm/control setpoints – SATEC PM130 PLUS Manual User Manual

Page 83

Advertising
background image

‎Chapter 5 Configuring

T H E P M 1 3 0 P L U S

General

M E T E R S E T U P

PM130 PLUS Powermeter Series

83

Display

Label

Option

Range

Default

Description

SCAL

Multiplier

1-9999

1

The value added to the

counter when a pulse is

detected on the pulse source

input

-

Counter Value

Displays the present counter

contents

Figure ‎5-11: General Setup Dialog Box – Pulse/Event Counters

You can preset a counter to a required value or clear it without affecting
the counter setup.

To preset or clear a counter:

1. Click the Online button on the PAS

toolbar before accessing the setup
dialog box.

2. Type in the required value into the

Counter Value field.

3. Click Send.

Configuring Alarm/Control Setpoints

The PM130 PLUS has an embedded logical controller that can perform
different actions in response to user-defined internal and external events.
Unlike a PLC, the meter uses a simplified programming technique based
on setpoints that allows the user to define a logical expression based on
measured analog and digital values that produce a required action.

The meter provides 16 control setpoints with programmable operate and
release delays. Each setpoint evaluates a logical expression with one
trigger argument. Whenever an expression is evaluated as “true”, the
setpoint performs a programmable action that can send a command to the
output relay, or increment a counter.