‎Chapter 5 Configuring

T H E P M 1 3 0 P L U S

General

M E T E R S E T U P

76

PM130 PLUS Powermeter Series

Figure ‎5-8: General Setup Dialog Box – Digital Inputs Dialog Box

The available options are shown in Table 22.

Table 22: Digital Input Options

Display

Label

Parameter

Options

Default

Description

Input Polarity NORMAL

INVERTING

NORMAL For the normal polarity, the open

to closed transition is considered

closed. For the inverting polarity,

the closed to open transition is

considered closed

PuLS

Pulse Input

Mode

PLS.A = PULSE MODE,

PLS.C = KYZ MODE

PULSE

MODE

In pulse mode, either leading, or

trailing edge of the input pulse is

recognized as an event. In KYZ

mode, both leading and trailing

edges of the input pulse are

recognized as separate events.

Polr

Pulse Polarity nor = NORMAL (N.O.),

InS = INVERTING (N.C.)

NORMAL For the normal polarity, the open

to closed transition is considered

a pulse. For the inverting polarity,

the closed to open transition is

considered a pulse.

It has no meaning in KYZ mode
where both transitions are used.

dbnc

Debounce
Time

1-100 ms

10 ms

The amount of time while the
state of the digital input should

not change to be recognized as a

new state. Too low debounce time

could produce multiple events on

the input change.

The debounce time is applied the same for all digital inputs. If you change
the debounce time for a digital input, the same debounce time is
automatically assigned to the others.