‎Chapter 5 Configuring

T H E P M 1 3 0 P L U S

General

M E T E R S E T U P

84

PM130 PLUS Powermeter Series

The logical controller provides very fast response to events. The scan time
for all setpoints is 1 cycle time (16.6 ms at 60Hz and 20 ms at 50/400
Hz).

Using the Front Display

Select SEtP from the main menu to enter the setup menu.

Use the UP and DOWN arrow buttons to scroll to the required setpoint.

To select a setpoint parameter:

1. Press the SELECT button to activate

the middle window.

2. Use the UP and DOWN arrow buttons to scroll to the required

parameter.

To change the parameter value:

1. Press the SELECT button to activate

the lower window.

2. Use the UP and DOWN arrow buttons to select the required

value.

3. Press ENTER to confirm the new setting or press ESC to

discard changes.

You are returned to the middle window
and can configure another parameter.

To store your new setpoint settings after you configured all
setpoint parameters:

1. Press the ENTER button when the

middle window is highlighted.

You are returned to the upper window
and can select another setpoint or exit
the menu.

2. Press ESC to exit the menu.

See the table below for the available setpoint options.

Using PAS

Select General Setup from the Meter Setup menu, and then click on the
Control/Alarm Setpoints tab.

The following table lists the available setpoint options.

Table 26: Setpoint Options

Display

Label

Option

Range

Description

TriG

Trigger parameter

See Appendix C

The trigger parameter that is used as an

argument in the logical expression

On

Operate limit

The threshold (in primary units) at which the

conditional expression would be evaluated to

true. Not applicable for digital triggers.