‎Chapter 5 Configuring

T H E P M 1 3 0 P L U S

General

M E T E R S E T U P

PM130 PLUS Powermeter Series

87

Table 27: Display Setup Options

Display

Label

Parameter

Options

Default

Description

UPdt

Display update rate

0.1-10.0 sec

1 sec

Defines the interval

between display updates

ScrL

Auto scroll interval

None,

2-15 sec

None

Defines the scroll interval

for the main data display or

disables auto scroll

rEtn

Auto return to the

main screen

diS = disabled,

En = Enabled

Enabled

Enables automatic return to

the main display if no

buttons are pressed for 5

minutes

bAr

Reference load current

for LED bar graph

0-10,000A

(0 = CT primary

current)

0

Defines the nominal load

(100%) level for the bar

graph display

Uolt

Primary/Secondary

volts units

Pri = primary

SEc = secondary

Primary

Selects primary or

secondary units for volts
display

Ph.P

Phase powers display

mode

diS, En

Disabled

Disables or enables phase

powers in the main display

Fund.

Fundamental

component display

mode

diS, En

Disabled

Disables or enables

fundamental values in the

main display

dAtE

Date order

dnY, ndY, Ynd

(d=day, n=month,

y=year)

mm.dd.yy Defines the date order in

the RTC display

rSt

Simple reset mode

PASS = password

protected
En = always

enabled

PASS

PASS = the simple reset is

not allowed if password
protection is enabled

En = enables the simple

reset buttons regardless of

password protection

brGt

Brightness

1-3

3

Sets the LED brightness

diAG

Diagnostic LED

diS, En

Disabled

Enables the diagnostic LED

FLSH

Flash Loader call

N/A

N/A

Launches the Flash Loader

Local Time Settings

This setup allows you to specify your time zone, daylight saving time, and
clock synchronization options.

Using the Front Display

Select rtc from the main menu. See

Viewing and Changing Setup Options

in Chapter 3 for information on configuring parameters via the front
display.

Using PAS

Select General Setup from the Meter Setup menu, and then click on the
Local Settings tab.