‎Chapter 5 Configuring

T H E P M 1 3 0 P L U S

Configuring

R E C O R D E R S

96

PM130 PLUS Powermeter Series

5.5 Configuring Recorders

The PM130E/EH PLUS has a 58-KByte onboard non-volatile memory for
data and event recording. The memory is fully configurable and can be
freely partitioned between log files.

The meter provides memory for a total of 3 log files:

Event log

Two data logs

The two data log files are pre-configured at the factory for recording a 15-
minute energy and demand profile and for the daily billing energy data
profile. If you wish to change the factory settings, follow the guidelines in
the next section.

Configuring Meter Memory

To view the present memory settings, select Memory/Log from the
Meter Setup menu, and then click on the Log Memory tab.

Figure ‎5-18: Log Setup Dialog Box – Log Memory Tab

The following table describes file options.

Option

Range

Description

Type

Wrap-around

Non-wrap

Wrap-around: recording continues over the oldest records.

Non-wrap: recording is stopped until the file is cleared.

Size

The size of memory allocated to the file.

Sections/Channels

0-8

The numbers of sections in a multi-section profile data log file

Num. of Records

0-65535

Allocates the file memory for predefined number of records

Record size

The size of the file record for a single channel or a single

section. It is set automatically depending on the file and on the

number of parameters in the data records

Parameters

0-9

The number of parameters in a single data log record

To change the file properties or to create a new file: