‎Chapter 5 Configuring

T H E P M 1 3 0 P L U S

General

M E T E R S E T U P

82

PM130 PLUS Powermeter Series

±2 mA: set the 1 mA scale to ½ of the required full-scale output
for both uni-directional and bi-directional parameters.

For example, to provide the 0 to 2 mA output current range for Volts
measured by the meter in the range of 0 to 120V, set the 1 mA scale to
60V; then the 120V reading will be scaled to 2 mA.

Configuring Counters

The PM130 PLUS has four six-digit general counters that can count pulses
delivered through the device digital inputs with a programmable scale
factor. Each counter can also be incremented in response to any internal
or external event, checked and cleared through the Control Setpoints.

Using the Front Display

Select Cnt from the main menu. This menu entry appears only if the
optional digital I/O module is plugged into the meter.

Use the UP and DOWN arrow buttons to scroll to the required counter.

To select a counter parameter:

1. Press the SELECT button to activate the

middle window.

2. Use the UP and DOWN arrow buttons to scroll to the required

parameter.

To change the parameter value:

1. Press the SELECT button to activate

the lower window.

2. Use the UP and DOWN arrow buttons to select the required

value.

3. Press ENTER to confirm the new parameter setting or press

ESC to discard changes.

You are returned to the middle window
and can configure another parameter.

To store your new settings:

1. When the middle window is highlighted,

press the ENTER button.

You are returned to the upper window
and can select another counter or exit
the menu.

2. Press ESC to exit the menu.

See Table 25 for the counter options.

Using PAS

Select General Setup from the Meter Setup menu, and then click on the
Pulse/Event Counters tab.

Table 25 lists available counter options.

Table 25: Counter Options

Display

Label

Option

Range

Default

Description

InP

Pulse Input

None,

DIGITAL INPUT

#1 - #12

None

Links a digital input to the

counter