‎Chapter 5 Configuring

T H E P M 1 3 0 P L U S

General

M E T E R S E T U P

PM130 PLUS Powermeter Series

85

Display

Label

Option

Range

Description

OFF

Release limit

The threshold (in primary units) at which the

conditional expression would be evaluated to

false. Defines the hysteresis for analog

triggers. Not applicable for digital triggers.

On d

Operate delay

0.1-999.9 sec

The time delay before operation when the

operate conditions are fulfilled

OFFd

Release delay

0.1-999.9 sec

The time delay before release when the

release conditions are fulfilled

Act

Action

See Appendix C The action performed when the setpoint

expression is evaluated to true (the setpoint

is in operated state)

Figure ‎5-12: General Setup Dialog Box – Control/Alarm Setpoints Tab

Using Numeric Triggers

For numeric (analog) triggers, you can specify two thresholds for each
trigger to provide hysteresis (dead band) for setpoint operations.

The Operate Limit defines the operating threshold, and the second Release
Limit defines the release threshold for the trigger. The trigger thresholds
are specified in primary units.

If you do not want to use hysteresis for the trigger, set the Release Limit
to the same value as the Operate Limit.

Using Binary Triggers

Binary (digital) triggers like digital inputs and relays are tested for
ON/CLOSED or OFF/OPEN status.