‎Chapter 5 Configuring

T H E P M 1 3 0 P L U S

General

M E T E R S E T U P

PM130 PLUS Powermeter Series

73

Wiring Mode

Description

3LL3

4-wire Wye using 2 PTs (2½ element), line-to-line voltage readings

3BLN3

3-wire Broken Delta using 2 PTs, 3 CTs (2½ element), line-to-neutral

voltage readings

3BLL3

3-wire Broken Delta using 2 PTs, 3 CTs (2½ element), line-to-line

voltage readings

In 4LN3, 3LN3 and 3BLN3 wiring modes, Min/Max volts, volt
demands and voltage harmonics represent line-to-neutral
voltages; otherwise, they will be line-to-line voltages.

Device Options

The Device Options setup allows changing user-configurable device
options or putting the meter into energy test mode.

Using the Front Display

Select OPtS from the main menu. See

Viewing and Changing Setup

Options

in Chapter 3 for information on configuring parameters via the

front display.

Using PAS

Select General Setup from the Meter Setup menu, and then click on the
Device Options tab.

Table 21 lists available device options.

Table 21: User-configurable Device Options

Display

Label

Parameter

Options

Default

Description

P.cAL

Power Calculation

Mode

rEAc = using reactive

power S=f(P, Q),

nAct = using non-active

power Q=f(S, P)

S=f(P, Q) The method used for calculating

reactive and apparent powers

(see

Power Calculation Modes

below)

roLL

Energy Roll Value

E, EH

10.E4 = 10000 kWh

10.E5 = 100000 kWh

10.E6 = 1000000 kWh

10.E7 = 10000000 kWh

10.E8 = 100000000 kWh

10.E9 = 1000000000 kWh

10000000 The value at which energy

counters roll over to zero

Ph.En

Phase Energy
Calculation

E, EH

diS = Disabled

En = Enabled

Disabled

Enables phase energy

calculations

tESt

Energy Test Mode

E, EH

OFF = disabled

Ac.Ei = Wh pulses

rE.Ei = varh pulses

Disabled

Setting this option puts the

meter into the energy test mode

(see

Energy Pulse LED

in

Chapter 3)

U.Str

Starting Voltage

1.5-5.0%

1.5%

The device starting voltage in

percent of FS (120V or 400V)