‎Appendix A Technical Specifications

146

PM135 Powermeter Series

A.12 Measurement Specifications

Table 21: Measurement Specifications Parameters

Parameter

Full Scale @ Input

Range

Accuracy

Range

%

Reading

% FS

Conditions

Voltage

120VxPT @ 120V
400VxPT @ 690V

0.2

0.02

10% to 120% FS 0 to 1,150,000 V

Starting voltage

1.5-5.0% FS (selectable)

Line current

CT

0.2

0.02

For In = 5A

1% to 200% FS

For In = 1A

5% to 200% FS

0 to 50,000 A

Starting current 0.1% FS

Active power

0.36

PT

CT @ 120V

1.2

PT

CT @ 690V

0.3

0.02

|PF|

0.5

1

-10,000,000 kW to

+10,000,000 kW

Reactive power

0.36

PT

CT@ 120V

1.2

PT

CT @ 690V

0.3

0.04

|PF|

0.9

1

-10,000,000 kvar to

+10,000,000 kvar

Apparent power 0.36

PT

CT @ 120V

1.2

PT

CT @ 690V

0.3

0.02

|PF|

0.5

1

0 to 10,000,000 kVA

Power factor

1.000

0.2

|PF|

0.5,

I

2% FSI

-0.999 to +1.000

Frequency

50 Hz

60 Hz

25 Hz

400 Hz

0.02

0.04

V

L-N

> 25V

15 Hz to 70 Hz

15 Hz to 70 Hz

15 Hz to 70 Hz

320 Hz to 480 Hz

Total Harmonic

Distortion, THD

V (I), %Vf (%If)

999.9

1.5

0.2

THD

1%,

V

10% FSV and

V

L-N

> 25V,

I

10% FSI

0 to 999.9

Total Demand

Distortion, TDD,

%

100

1.5

TDD

1%,

I

10% FSI,

V

L-N

> 25V

0 to 100

Active energy

Import & Export

Class 0.5S under conditions as per

IEC 62053-22:2003

0 to 999,999,999 kWh

Reactive energy

Import & Export

Class 0.5S under conditions as per

IEC 62053-22:2003, |PF|

0.9

0 to 999,999,999 kvarh

Apparent energy

Class 0.5S under conditions as per

IEC 62053-22:2003

0 to 999,999,999 kVAh

PT - external potential transformer ratio

CT - primary current rating of the external current transformer

FSV - voltage full scale

FSI - current full scale

Vf

- fundamental voltage

If

- fundamental current

NOTES

1. Accuracy is expressed as

(percentage of reading +

percentage of full scale)

1 digit. This does not

include inaccuracies introduced by the user's
potential and current transformers. Accuracy
calculated at 1second average.

1

@ 80% to 120% of voltage FS, 1% to 200% of current FS and frequency 50/60 Hz