‎Chapter 5 Configuring the PM135

Configuring Communications

PM135 Powermeter Series

71

Figure ‎5-1: Communication Setup Dialog Box – Serial Ports Setup Tab

See Table 3

below for available communication options.

Table 3: COM Port Options

Parameter

Options

Default

Description

Protocol

MODBUS ASCII

SATEC ASCII

MODBUS RTU

DNP3

IEC 60870-5

PROFIBUS DP (COM2)

MODBUS

RTU

The communications

protocol for the port

Not changeable on COM2

with the PROFIBUS

module

Interface

COM1: 485 = RS-485

COM2:

232 = RS-232

485 = RS-485

422 = RS-422

Eth = Ethernet

PRO = PROFIBUS DP

GPRS = GPRS modem

RS-485

Communication interface.

Not changeable on COM2

with the Ethernet and

PROFIBUS modules

Device address SATEC ASCII: 0-99

MODBUS: 1-247

DNP3: 0-65532

PROFIBUS: 0-126

1

(126 for

PROFIBUS)

Device network address

Baud rate

300 bps-115.2 kbps

9600 bps

The port baud rate

Data format

7E, 8N, 8E

8N

Data format and parity.

7E data format should not

be used with the MODBUS

RTU and DNP3 protocols

Response delay 0-1000 ms

5 ms

The minimum time after

the last request character

is received to start the
transmission.

NOTES:

1. The meter provides the permanent

MODBUS TCP server on port 502.