Setting up gprs network – SATEC PM135 Manual User Manual

Page 73

Advertising
background image

‎Chapter 5 Configuring the PM135

Configuring Communications

PM135 Powermeter Series

73

Figure ‎5-2: Communication Setup Dialog Box – Network Setup Tab

The table below lists available network options.

Table 4: Ethernet Setup Options

Parameter

Options

Default

Device IP Address

192.168.0.203

Network Subnet Mask

255.255.255.0

Network Default Gateway

192.168.0.1

TCP Service Port

502 = Modbus/TCP

20000 = DNP3/TCP

502

NOTES

1. The meter provides the permanent

MODBUS TCP server on port 502.

2. Selecting the DNP3 TCP service port

launches the second DNP3 TCP
server

allowing

simultaneous

connections on both TCP ports.
Selecting the MODBUS TCP port
disables the DNP3 TCP server.

The TCP service port can also be changed trough the COM2
serial port setup. Changing the communication protocol for the
port automatically changes the TCP port for the Ethernet.

3. When you change the device

network

settings

through

the

Ethernet port, the device port
restarts so communication will be
temporarily lost. You may need to
wait some additional time until PAS
restores a connection with your
device.

Setting Up GPRS Network

The PM135 can provide wireless GPRS communications with the remote
MODBUS/TCP server via the GPRS modem module. See

Connecting a