‎Chapter 5 Configuring the PM135

General Meter Setup

88

PM135 Powermeter Series

Table 14: Counter Options

Option

Range

Default

Description

Pulse Input

None,
DIGITAL INPUT #1 - #12

None

Links a digital input

to the counter

Multiplier

1-9999

1

The value added to

the counter when a

pulse is detected on

the pulse source

input

Counter Value

Displays the present

counter contents

Figure ‎5-11: General Setup Dialog Box – Pulse/Event Counters

You can preset a counter to a required value or clear it without affecting
the counter setup.

To preset or clear a counter:

1. Click the Online button on the PAS

toolbar before accessing the setup
dialog box.

2. Type in the required value into the Counter Value field.

3. Click Send

Configuring Alarm/Control Setpoints

The PM135 has an embedded logical controller that can perform different
actions in response to user-defined internal and external events. Unlike a
PLC, the meter uses a simplified programming technique based on
setpoints that allows the user to define a logical expression based on
measured analog and digital values that produce a required action.

The meter provides 16 control setpoints with programmable operate and
release delays. Each setpoint evaluates a logical expression with one
trigger argument. Whenever an expression is evaluated as “true”, the
setpoint performs a programmable action that can send a command to the
output relay, or increment a counter.

The logical controller provides very fast response to events. The scan time
for all setpoints is 1 cycle time (16.6 ms at 60Hz and 20 ms at 50/400
Hz).