‎Chapter 5 Configuring the PM135

General Meter Setup

86

PM135 Powermeter Series

Using PAS

Select General Setup from the Meter Setup menu, and then click on the
Analog Outputs tab.

Figure ‎5-10: General Setup Dialog Box – Analog Outputs Tab

The available analog output options are described in Table 13.

Table 13: Analog Output Options

Option

Range

Description

AO type

0-1mA

±1mA

0-20mA

4-20mA

The analog output type. When connected to the

meter, shows the actual AO type received from

the device. When working off-line, select the

analog output option corresponding to your

analog module.

Output

parameter

See Appendix B Selects the measured parameter to be

transmitted through the analog output channel.

Zero scale

Defines the low engineering scale (in primary

units) for the analog output corresponding to a

lowest (zero) output current (0 or 4 mA)

Full scale

Defines the high engineering scale (in primary

units) for the analog output corresponding to a

highest output current (1 or 20 mA)

When you select an output parameter for the analog output channel, the
default engineering scales are set automatically. They correspond to the
maximum available scales. If the parameter actually covers a lower range,
you can change the scales to provide a better resolution on an analog
output.

Scaling Non-Directional Analog Outputs

For non-directional analog outputs with a 0-1mA, 0-20mA or 4-20mA
current option, you can change both zero and full engineering scales for
any parameter. The engineering scale need not be symmetrical.