Gprs/gsm modem module – com2 gprs connection – SATEC PM135 Manual User Manual

Page 39

Advertising
background image

‎Chapter 2 Installation

Communications Connections

PM135 Powermeter Series

39

The RS-232/422-485 module TERMINALS are for use only

with equipment which has no live parts which are
ACCESSIBLE

The RATING of the insulation of the external equipment for

use with The RS-232/422-485 module, shall comply
according to Installation Category II for insulation to be
suitable for SINGLE FAULT CONDITION

The external equipment TERMINAL connection type is

normally terminal block for wire size 14 AWG (up to 1.5
mm²) – RS-422/485 port and DB9 male-to-female cable
more than 22 AWG (0.3mm²)

The type of equipment that might be connected to the

TERMINAL is:

Personal Computer – PC or LAPTOP

GPRS/GSM modem module – COM2 GPRS connection

A GSM/GPRS modem module can be connected to the meter COM2 port to
provide communications with the remote MODBUS/TCP server via a
wireless GPRS network.

Figure ‎2-32: GSM/GPRS modem Module

The GSM/GPRS SIM must not have any incoming voice call.
The customer must require from the Service Provider for DATA
services only
The GPRS modem module can be equipped with two different
antennas: internal Antenna for installation into plastic closet or
no-metallic environment. For metallic installation use external
antenna

See

Setting Up GPRS Network

in Chapter 5 for information on configuring

GPRS communications in your meter.