‎Chapter 5 Configuring the PM135

Configuring Billing/TOU

PM135 Powermeter Series

99

Figure ‎5-16: Energy/TOU Setup Dialog Box – Billing/TOU Registers tab

2. Configure the register options

according to the valid parameters
shown in Table 18.

Table 18: Billing/TOU Register Options

Parameter

Options

Default

Description

Billing/TOU Registers

TOU

Unchecked

Checked

Unchecked Links tariff registers to the selected energy

source

Use Profile

Unchecked

Checked

Checked

Enables recording energy registers in a daily

billing profile file (both total and tariff

registers if TOU is enabled).

Dmd Profile

Unchecked

Checked

Unchecked Enables recording maximum demand

registers in a daily billing profile file (both

total and tariff registers if TOU is enabled)

Sum Profile

Unchecked

Checked

Checked

Enables recording total (summary) registers

in a daily billing profile file.

Units

kWh, kvarh, kVAh,
m3, CF (cubic

foot), CCF

(hundred cubic

feet)

None

The register measurement units. When a
register is linked to an internal energy

source, it is set automatically. When an

external pulse source is used, the user can

select a measurement unit for the register.

Register Source List

Source Input

None

kWh Import

kWh Export

kvarh Import
kvarh Export

kVAh,

DI1-DI12

None

Links an energy source to the register

Multiplier

0.001 to 100.000

1.000

The multiplication factor for the energy

source. Unchangeable for internal energy

sources.

Target

Reg#1- Reg#4

None

Defines the target billing register for the

energy source. It is set automatically.