‎Chapter 5 Configuring the PM135

General Meter Setup

78

PM135 Powermeter Series

5.2 General Meter Setup

Basic Meter Setup

This section describes how to configure the PM135 for your particular
environment and application.

Before operating your meter, provide the device with basic information
about your electrical network.

Using the Front Display

Select the Basic Setup entry from the Device Setup menu. See

Viewing

and Changing Setup Options

in Chapter 3 for information on configuring

parameters via the front display.

Device Setup

Reset
Real Time Clock
Display Setup

Basic Setup

Device Options
COM1 Setup
COM2 Setup

Using PAS

Select General Setup from the Meter Setup menu. See the table below
for the Basic Setup options.

Table 8: Basic Setup Options

Parameter

Options

Default

Description

Basic Configuration

Wiring Mode

See

Table 9

4Ln3

The wiring connection of the device

PT Ratio

1.0-6500.0

1.0

The phase potential transformer’s

primary to secondary ratio

PT Ratio Multiplier

Ч1, Ч10

Ч1

PT Ratio multiplication factor. Used

in extra high voltage networks to

accommodate the PT ratio for

500 kV and higher networks.

CT Primary Current

1-50000 A

5 A

The primary rating of the phase

current transformer

Nominal Frequency

50,60,25,400 Hz 60 Hz

The nominal line frequency

Maximum Demand
Load Current

0-50000 A

0

The maximum demand load
current (0 = CT primary current)

Power block demand
period

E, EH

1, 2, 3, 5, 10, 15,

20, 30, 60 min,

E=external sync

15 min

The length of the demand period

for power demand calculations. If

the external synchronization is

selected, a pulse front on the

digital input DI1 denotes the start

of the demand interval.

The number of

blocks in the sliding
demand window

E, EH

1-15

1

The number of blocks to be

averaged for sliding window

demands