‎Chapter 3 Using Front Display

Display Operations

58

PM135 Powermeter Series

Basic Settings Display

The basic settings display shows basic device settings that can be required
for immediate inspecting while meter testing and at the time of
installation. Use the UP/DOWN button to scroll through the settings

Device wiring mode (see

Basic Meter Setup

for full

list of wiring modes), external potential transformer

ratio and the nominal device voltage.

Primary ratings of the external current transformers

(main and auxiliary current inputs) and the nominal

device frequency

Power demand period (number of blocks x block
demand period), and voltage and ampere demand

periods.

Device Info Display

The device info display provides different service information that may be
required for meter identification and inspection, like product/module and
firmware information, I/O module type, communication settings, and so
on. Use the UP/DOWN button to scroll through the device info.

Meter identification info

Meter communication info

Load Bar Graph

The load bar graph displays the amount, in percent (40% to 110%), of
the present current load with respect to user-defined nominal load
current. The reference nominal current can be set up in amps through the
display setup (see

Configuring the Display

). If it is set to 0 (default), the

current load is referenced to the specified CT primary current.