‎Chapter 5 Configuring the PM135

Configuring Billing/TOU

98

PM135 Powermeter Series

5.4 Configuring Billing/TOU

The TOU battery-backed clock unit is highly recommended in case
of using time-scheduled tariff rates, otherwise a long power
outage may cause the meter clock to lose time so your tariff
counters would not comply with the calendar schedule.

Billing Energy Registers

The PM135E/EH has 4 fully programmable billing energy registers that
can be linked to any internal energy source or to an external pulse source
that delivers pulses through the meter digital inputs.

Any energy register can provide either a single-tariff energy accumulation
or be individually linked to the TOU system providing both total and multi-
tariff energy billing.

Tariff Rates

The meter tariff structure supports 8 different tariff rates using an
arbitrary tariff schedule. A total of 4 types of days and 4 seasons are
supported with up to eight tariff changes per day.

Maximum Demand Registers

Any of billing energy registers can be individually linked to the maximum
demand register providing the same demand tariff structure as you
selected for energy registers.

Recording Billing Data and Load Profiling

The PM135E/EH can provide automatic recording of the daily energy and
maximum demand profile to a data log file. Maximum demand profiling
can be individually configured for every register.

See

Factory Preset Data Log Files

in Chapter 5 and

Billing Profile Log File

in Appendix E for more information on the file layout and contents.

To configure the billing registers and the tariff system in your
meter:

1. Link the billing registers to the

respective energy sources.

2. Configure the options for the

registers to whether the only
totalization or both total and tariff
registers would be used, and
whether daily profiling should be
enabled for the energy usage and
maximum demand registers.

3. Configure the daily tariff schedule

using the TOU daily profiles for all
types of days and seasons.

4. Configure the season tariff schedule

using the TOU calendar.

Configuring Billing/Tariff Registers

To configure the billing/TOU registers in your meter:

1. Select Energy/TOU from the

Meter Setup menu.