‎Appendix F Data Scales

164

PM135 Powermeter Series

Appendix F Data Scales

The maximum values for volts, amps and power in the PM135 setup and
in communications are limited by the voltage and current scale settings.
See

Device Options

in Chapter 4 on how to change the voltage and

current scales in your meter.

The following table shows the meter data scales.

Table 27: Data Scales Values

Scale

Conditions

Range

Maximum voltage
(V max)

All configurations

Voltage scale

PT Ratio, V

1

Maximum current

(I max)

All configurations

Current scale

CT Ratio, A

2, 3

Maximum Power

4

Wiring 4LN3, 3LN3, 3BLN3

V max

I max

3, W

Wiring 4LL3, 3LL3, 3BLL3,

3OP2, 3OP3, 3DIR2

V max

I max

2, W

Maximum frequency

25, 50 or 60 Hz

100 Hz

400Hz

500 Hz

1

The default voltage scale is 144V. The recommended voltage scale is

120V+20% = 144V for using with external PT’s, and 690V+20% = 828V
for a direct connection to power line.

2

CT Ratio = CT primary current/CT secondary current

3

The default current scale is 2

CT secondary (2.0A with 1A secondary

and 10.0A with 5A secondary).

4

Maximum power is rounded to whole kilowatts. With PT=1.0, it is

limited to 9,999,000 W.