‎Chapter 5 Configuring the PM135

General Meter Setup

PM135 Powermeter Series

83

Setpoints

), or can be linked to general pulse counters to count incoming

pulses (see

Configuring Counters

). They can also be linked to the

Billing/TOU registers to count pulses from external wattmeters or gas and
water meters.

Using PAS

Select General Setup from the Meter Setup menu, and then click on the
Digital Inputs tab.

Figure ‎5-8: General Setup Dialog Box – Digital Inputs Dialog Box

The available options are shown in Table 11.

Table 11: Digital Input Options

Parameter

Options

Default

Description

Pulse Input

Mode

PULSE MODE

KYZ MODE

PULSE

MODE

In pulse mode, either leading, or

trailing edge of the input pulse is

recognized as an event. In KYZ

mode, both leading and trailing

edges of the input pulse are

recognized as separate events.

Pulse Polarity NORMAL (N.O.),

INVERTING (N.C.)

NORMAL For the normal polarity, the open

to closed transition is considered

a pulse. For the inverting polarity,

the closed to open transition is

considered a pulse.

It has no meaning in KYZ mode

where both transitions are used.

Debounce

Time

1-100 ms

10 ms

The amount of time while the

state of the digital input should

not change to be recognized as a

new state. Too low debounce time

could produce multiple events on

the input change.

The debounce time is applied the same for all digital inputs. If you change
the debounce time for a digital input, the same debounce time is
automatically assigned to the others.