‎Chapter 5 Configuring the PM135

Configuring Communications

PM135 Powermeter Series

77

Figure ‎5-5: TCP Notification Client Setup Tab

The following table lists available client options.

Table 7: TCP Notification Client Setup Options

Parameter

Options

Default

Description

Client Enabled

NO, YES

NO

Enables operations of the

notification client

Server IP Address

192.168.0.3

The IP address of the notification

server

Server Port

0-65535

502

The TCP service port of the

notification server

Message Exchange

Address

0-65535

1000

The start address of a block

of 16 MODBUS registers for

receiving notification messages

Connections with a remote server are triggered via programmable
setpoints. To send event notifications to a server, configure a setpoint to
respond to desired triggers or to periodic time events and put the
"Notification" action to the setpoint action list (see

Configuring

Alarm/Control Setpoints

).

See the PM135 Modbus Reference guide for more information on operation
of the notification client and the notification message structure.