Prepare for installation, Mounting considerations, Operating conditions and temperatures – Rockwell Automation 23P PowerFlex DC Stand Alone Regulator and Gate Amplifier User Manual

Page 13: Chapter 2, Stand alone regulator, Installation, wiring and, Configuration, Prepare for installation mounting considerations

Advertising
background image

Rockwell Automation Publication 23P-UM001D-EN-P - July 2012

13

Chapter

2

Stand Alone Regulator Installation, Wiring

and Configuration

Prepare for Installation

Prior to installation of the PowerFlex DC Stand Alone Regulator (SAR) read the
General Precautions on

page 9

.

Mounting Considerations

Operating Conditions and Temperatures

The SAR is designed to operate at 0°…50° C (32°… 122° F) surrounding air
temperature without derating. The unit must be mounted in a clean, dry location.
Contaminants such as oils, corrosive vapors and abrasive debris must be kept out
of the enclosure. NEMA/UL Type Open, IP20 enclosures are intended for
indoor use primarily to provide a degree of protection against contact with
enclosed equipment. These enclosures offer no protection against airborne
contaminants.