Stand Alone Regulator Installation, Wiring and Configuration

Chapter 2

Example 2:

CT, Burden Resistor and Gain Calculation

Minimum CT Primary based on IOC trip point of 2.5 x Power Module rating

Maximum CT ratio based on Gain Range of Scaling Op-Amp in the Current
Feedback circuit

Input Values

Units

Description

IdN_pm_rtg: = 226

Amp

Power module rating

Rb:= 2.5

Ohms

Jumpers J4 and J5 in the “On”
position. See

Figure 13 on

page 39

for jumper locations.

CT_pri: = 2000

Amp

CT_sec: = 1

Amp

Value/Calculation

Units

Description

IOC_mult: = 2.5

CT_pri_min: =
IOC_mult x IdN_pm_rtg x 0.85

0.85 is the ratio of AC to DC
current

CT_pri_min = 480

Amp

Based on IOC trip point

CT_ratio_min_based_on_ioc: = CT_pri_min / CT_sec

CT_ratio_min_based_on_ioc = 480

Based on IOC trip point

Value/Calculation

Units

Description

CT_ratio_max: = 1.2 x (IdN_rtg x Rb) / 0.612

CT_ratio_max = 1.108 x 10

3

Based on Gain <= 1.2

Value/Calculation

Units

Description

Vf_at_IdN_pm_rtg = 0.612

Volts

Fixed Value

CT_ratio: = CT_pri / CT_sec

CT_ratio = 2 x 10

3

Ib_at_IdN_pm_rtg: = IdN_pm_rtg / CT_ratio

Ib_at_IdN_pm_rtg = 0.113

Amps

Vb_at_IdN_pm_rtg: = (IdN_pm_rtg / CT_ratio) x Rb

Vb_at_IdN_pm_rtg = 0.283

Volts

Gain_Required: = Vf_at_IdN_pm_rtg /
Vb_at_IdN_pm_rtg

Gain_Required = 2.166

Note: Required Gain = 2.166,
which is greater than the
Recommended Gain <= 1.2 (for
best accuracy)