Chapter 2 Stand Alone Regulator Installation, Wiring and Configuration

Field Power Module Bridge

and Ground Wiring

The SAR contains a two quadrant field power module bridge. The field bridge
input circuit is rated for 100VAC…460VAC, ±10%, 50/60 Hz. The input and
output connections to/from the field bridge are on the bottom of the SAR as
shown.

An external transformer with appropriate primary fusing is required to supply the
field. External fusing is also required at the input terminals V1 and U1 to protect
the field bridge. The recommended fuse types are shown in the

Table 4 on

page 21

.

The SAR motor field current must configured with a hardware DIP switch and in
firmware. See

SAR Motor Field Current Configuration on page 26

for more

information.

Figure 5 - Field Power Module Bridge Terminal Block and Ground Connection

Table 3 - Field Power Module Bridge and Ground Terminal Specifications

No. Terminal

Description

Wire Size Range

Recommended

Torque

Maximum

Minimum

V1, U1

AC Input Power

25.0 mm

2

(2 AWG)

10.0 mm

2

(10 AWG)

4.0…4.5 N•m
(35.4…39.8 lb•in)

C1, D1

DC Output Power
to Motor Field

PE

Safety Ground

(1)

(1) See

Safety Ground (PE) on page 21

for more information.

16.0 mm

2

(6 AWG)

10.0 mm

2

(8 AWG)

6.0…8.0 N•m
(53.1…70.8 lb•in)