Chapter 2 Stand Alone Regulator Installation, Wiring and Configuration

Figure 6 - AC /DC Voltage Feedback (KP) and Motor Armature Voltage Feedback

(KA) Terminal Blocks

Table 5 - AC / DC Voltage and Motor Armature Voltage Feedback Terminal

Specifications

DC Feedback Fusing Requirements

The recommended fuses are:

• Bussmann fuse FWP-5A14F (5 A, 700V, Type FWP, 14 x 51mm), or

equivalent.

Note: The AC voltage feedback inputs on the SAR are fused internally.

No. Terminal

Description

Wire Size Range

Recommended

Torque

Maximum

Minimum

W, V, U

AC Input
Feedback
(connector KP)

6.0 mm

2

(10 AWG)

0.2 mm

2

(24 AWG)

0.7…0.8 N•m
(6.2…7.1 lb•in)

D, C

DC Output
Feedback
(connector KP)

1A1, A1,
1A2, A2

Motor Armature
Voltage Feedback
(connector KA)

1 2 3 4 5 6 7 8

V1 U1 C1 D1

KPT21

KPT11

KPT31

PE

D C W V U

1A1

(C)

A1 1A2

(D)

A2

AC /DC Voltage
Feedback (KP)
Terminal Block

Bottom View of SAR

Motor Armature
Voltage Feedback
(KA) Terminal
Block

1

2

1

1

2