Rockwell Automation Publication 23P-UM001D-EN-P - July 2012

23

Stand Alone Regulator Installation, Wiring and Configuration

Chapter 2

Connector KP Wiring

• Connect the motor armature terminal C to terminal C on connector KP
• Connect the motor armature terminal D to terminal D on connector KP

Connector KA Wiring

Connector KA must be wired to provide DC voltage feedback to the field
regulator to control the field current based on the armature voltage. Terminal
1A1 is connected internally to terminal C (on connector KP) and terminal 1A2
is connected internally to terminal D (on connector KP). The default
configuration is shown in

Figure 7

and is wired as follows:

• Jumper terminal 1A1 to terminal A1
• Jumper terminal 1A2 to terminal A2

The jumpers will provide the field regulator with the power module/armature
voltage feedback. This is the default wiring scheme for connector KA at the
factory.