A - specifications, Stand alone regulator, Electrical – Rockwell Automation 23P PowerFlex DC Stand Alone Regulator and Gate Amplifier User Manual

Page 71: Environmental, Power dissipation, Gate amplifier, Appendix a, Specifications, Stand alone regulator gate amplifier, Appendix

Advertising
background image

Rockwell Automation Publication 23P-UM001D-EN-P - July 2012

71

Appendix

A

Specifications

Stand Alone Regulator

Electrical

Field Bridge
Input Voltage

100VAC…460VAC, ±10%, 50/60 Hz

Control Supply
Input Current

115VAC/1AAC or 230VAC/0.5AAC

Environmental

Operating Temperature 0

° C to 50 ° C (32 ° F to 122 ° F)

Storage Temperature

-25

° C to 55° C (-13 ° F to 131 ° F)

Relative Humidity

5% to 95%, Non-condensing

Note: Contamination from oils, corrosive vapors and abrasive debris must be
kept out of the enclosure.

Power Dissipation

Gate Amplifier

Electrical

Control Input

120VAC ±10%, 1.9 A, 47-63 Hz

Replacement fuse

Littelfuse 312005, 5 A, 250VAC, 3AG Time Delay
or equivalent.

Environmental

Operating Temperature 0

° C to 50 ° C (32 ° F to 122 ° F)

Storage Temperature

-40

° C to 70 ° C (-40 ° F to 158 ° F)

Relative Humidity

5% to 95%, Non-condensing

Note: Contamination from oils, corrosive vapors and abrasive debris must be
kept out of the enclosure.

Catalog

Number

Power Bridge AC

Input

Field Ratings

Total Watts

Loss

[V

AC

]

Input [V

AC

] Input [A

AC

]

Output [A

DC

] [W]

23PMD4

(230 to) 500

(230 to) 460

40

40

303

23PMD7

(230 to) 500

(230 to) 460

70

70

357

23PMF4

(575 to) 690

(230 to) 460

40

40

374

23PMF7

(575 to) 690

(230 to) 460

70

70

428

Advertising