Gate amplifier, cascade configurations, Gate amplifier, Powerflex dc stand-alone regulator – Rockwell Automation 23P PowerFlex DC Stand Alone Regulator and Gate Amplifier User Manual

Page 54

Advertising
background image

54

Rockwell Automation Publication 23P-UM001D-EN-P - July 2012

Chapter 3 Gate Amplifier Installation and Wiring

Gate Amplifier, Cascade Configurations

It is permissible to cascade Gate Amplifiers. The time delay through the Gate
Amplifier is 0.5 μSec. This amount of time delay is not significant with regard to
the gate firing of parallel power modules. For any configuration with multiple
Gate Amplifiers, be sure to connect the Ready relay into the “Run Permissive”
circuit.

The external +48V power supply cannot be used on a Gate Amplifier or SD3000

PLUS whose output acts as an input source for a downstream Gate Amplifier.
The continuous application of the high amplitude gate pulses to the input will
cause excessive heating of the components of the input stage. If the external 48V
power supply is used, the interlocking relay must also be used as described in the
“EXT GATE P/S” section on

page 51

.

Illustrations are included for both the Stand Alone Regulator (see

Figure 21

below and

Figure 22 on page 55

) and the SD3000

PLUS (see

Figure 23 on

page 56

and

Figure 24 on page 57

).

Figure 21 - Cascading Gate Amplifiers Using the Stand Alone Regulator

REV Output Cables

SD3K-CBLGSCLIRxxx

+

-

SD3K
FWD IN

SD3K
REV IN

PFDC

Gate Input

FWD

REV

RDY

Ext. P/S

120VAC

Gate Amplifier

FWD Output Cables

SD3K-CBLGSCLIFxxx

To Gate Amplifier,
1 of 4, SD3K-FWD Input

To Gate Amplifier,
2 of 4, SD3K-FWD Input

To Gate Amplifier,
3 of 4, SD3K-FWD Input

To Gate Amplifier,
4 of 4, SD3K-FWD Input

To Gate Amplifier,
1 of 4, SD3K-REV Input

To Gate Amplifier,
2 of 4, SD3K-REV Input

To Gate Amplifier,
3 of 4, SD3K-REV Input

To Gate Amplifier,
4 of 4, SD3K-REV Input

+

-

SD3K
FWD IN

SD3K
REV IN

PFDC

Gate Input

FWD

REV

RDY

Ext. P/S

120VAC

Gate Amplifier

1 of 4

From Gate Amplifier,

FWD Output

From Gate Amplifier,

REV Output

To Forward

Power Modules

To Reverse

Power Modules

+

-

SD3K
FWD IN

SD3K
REV IN

PFDC

Gate Input

FWD

REV

RDY

Ext. P/S

120VAC

Gate Amplifier

4 of 4

From Gate Amplifier,

FWD Output

From Gate Amplifier,

REV Output

To Forward

Power Modules

To Reverse

Power Modules

Up to Four

Gate Amplifier

PowerFlex DC

Stand-alone Regulator

KPT11

(15 Pin D-Shell)

Field Supply
40 A or 70 A

(2 Quad)

To Motor

Field

Gate Cable

Caution: Do NOT use the external power supply (Ext. P/S)
when the gate pulse output is connected to the input of a
“downstream” Gate Amplifier(s). Only use the external power
supply on a final stage Gate Amplifier(s) that provides the
gate pulses to the power module.

C1 D1

D C W V U

1A1 A1 1A2 A2

1 2 3 4 5 6 7 8

KPT31

KA

KP

Power Module

AC / DC

Feedback

Power Module

Armature Voltage

Feedback

Power Module

Thermostat and

CT Feedback

V1 U1

All Terminals are located

on the bottom of the unit.

Advertising