Checking the Maximum Voltage Feedback to Regulator

Binary Gain Calculation and Checking Gain Error

Binary_Sw_Setting = 47.268

Value to use - 47, Binary = 101111

For DIP switch SW3 and SW4 layout, refer to

Table 14

-

Binary Gain Amp DIP

Switch to Bit Layout on page 39

.

Resistor values are in K Ohms

Vb_at_IdN_pm_rtg = 0.565

Volts

Gain_Required: = Vf_at_IdN_pm_rtg /
Vb_at_IdN_pm_rtg

Gain_Required = 1.083

Note: Required Gain = 1.083,
which is within the
Recommended Gain <= 1.2 (for
best accuracy)

Value/Calculation

Units

Description

Binary_Sw_Setting: = 51.2 / Gain_Required

Binary_Sw_Setting = 47.268

Ib_at_IOC: = (IdN_pm_trg x IOC_mult / CT_ratio)

Ib_at_IOC = 0.282

Amps

Vb_at_IOC: = (IdN_pm_rtg x IOC_mult / CT_ratio)

Vb_at_IOC = 1.412

Volts

V_curr_fdbk_to_reg_at_IOC: = Gain_Required x
Vb_at_IOC

Maximum allowable value of
V_curr_fdbk_to_reg_at_IOC =
2.5V

V_curr_fdbk_to_reg_at_IOC = 1.53

Volts

Value/Calculation

Units

Description

MSB

LSB

Bit Value

B11: = 0 B10: = 0 B9: = 0

B8: = 0

B7: = 0

B6: = 0

B5: = 1

B4: = 0

B3: = 1

B2: = 1

B1: = 1

B0: = 1

DIP Switch

Setting

SW3-1
= Off

SW3-2
= Off

SW3-3
= Off

SW3-4
= Off

SW4-1
= Off

SW4-2
= Off

SW4-3
= On

SW4-4
= Off

SW4-5
= On

SW4-6
= On

SW4-7
= On

SW4-8
= On

R_fdbk: =

1

B11 / 0.50 + B10 / 1 + 9 / 2 + B8 / 4 + B7 / 8 + B6 / 16 + B5 / 32 + B4 / 64 + B3 / 128 + B2 / 256 + B1 / 512 + B0 / 1024