Table 10 - Recommended Welding Cable for High Frequency Grounding/Bonding

DC Drive High Frequency Grounding of Adjacent Cabinet Panels

Unless there is good continuity from panel to panel, the potential between the
panels will be different.

Notes on cabinet grounding:

• This grounding scheme is for high frequency grounding only. The

customer is responsible for all safety grounds and meeting local and state
equipment grounding codes.

• If the DC Drive Regulator components are mounted to a sub-panel, then

there must be a 1/0 Welding cable ground jumper between the sub-panel
and the main cabinet control panel.

Figure 18 - DC Drive High Frequency Grounding / Bonding Configuration

Drive System Nominal

Motor FLA Per Section

Recommended Welding

Cable Size

Cable Type

100…3000 Amps

2/0

Anixter #5J-2021 or Equivalent

3001…5000 Amps

3/0

Anixter #5J-3031 or Equivalent

5001…9000 Amps

250 MCM

Anixter #5J-2501 or Equivalent

9001…20000 Amps

500 MCM

Anixter #5J-5001 or Equivalent

Power

Transformer

Drive

Cabinet

Drive

Cabinet

Power

Entry

Bay

Gnd

Drive

Cabinet

M

Drive

Cabinet

Drive

Cabinet

M

Internal Bay to Bay
Grounding Cable Detail:
#1/0 kcmil compression lug
Burdy - YA25L6 or equal
Stud size = 1/2 inch
(both ends of jumper)

#1/0 kcmil welding cable
anixter #5J1011 or equal
Length determined in the field
to suit need

Internal “Bay to Bay”
1/0 Ground Cable
(see detail at right)

One Welding Cable,
Fine Strand.
See

Table 10

for

Recommended Size.

Ground to Frame of Transformer. Ensure that
all Paint is Removed Before Attaching Lugs,
or “CAD Weld” Wire to the Frame.

One Welding Cable,
Fine Strand.
See

Table 10

for

Recommended Size.

One Welding Cable,
Fine Strand.
See

Table 10

for

Recommended Size.

One Welding Cable,
Fine Strand.
See

Table 10

for

Recommended Size.

One Welding Cable,
Fine Strand.
See

Table 10

for

Recommended Size.