Minimum Mounting Clearances
Minimum clearance requirements (indicated in
) are intended to be from enclosure to enclosure.
Other objects can occupy this space; however, reduced airflow may cause
protection circuits to fault the SAR. The SAR must be mounted in a vertical
orientation as shown and must not be mounted at an angle greater than 30
degrees from vertical. In addition, inlet air temperature must not exceed the
product specification.
Figure 2 - Drive Enclosure Minimum Mounting Clearances
Min. 10 0 mm
(0.4 in.)
Min. 150 mm
(6.0 in.)
Min. 150 mm
(6.0 in.)
Min. 150 mm
(6.0 in.)
Min. 150 mm
(6.0 in.)
Min. 10 0 mm
(0.4 in.)
Min. 50 mm
(2.0 in.)
Min. 10 0 mm
(0.4 in.)
Airflow through the unit
must not be impeded.