Minimum mounting clearances – Rockwell Automation 23P PowerFlex DC Stand Alone Regulator and Gate Amplifier User Manual

Page 14

Advertising
background image

14

Rockwell Automation Publication 23P-UM001D-EN-P - July 2012

Chapter 2 Stand Alone Regulator Installation, Wiring and Configuration

Minimum Mounting Clearances

Minimum clearance requirements (indicated in

Figure 2

-

Drive Enclosure

Minimum Mounting Clearances

) are intended to be from enclosure to enclosure.

Other objects can occupy this space; however, reduced airflow may cause
protection circuits to fault the SAR. The SAR must be mounted in a vertical
orientation as shown and must not be mounted at an angle greater than 30
degrees from vertical. In addition, inlet air temperature must not exceed the
product specification.

Figure 2 - Drive Enclosure Minimum Mounting Clearances

Min. 10 0 mm

(0.4 in.)

Min. 150 mm

(6.0 in.)

Min. 150 mm

(6.0 in.)

Min. 150 mm

(6.0 in.)

Min. 150 mm

(6.0 in.)

Min. 10 0 mm

(0.4 in.)

Min. 50 mm

(2.0 in.)

Min. 10 0 mm

(0.4 in.)

Airflow through the unit
must not be impeded.