Gate amplifier, Power modules – Rockwell Automation 23P PowerFlex DC Stand Alone Regulator and Gate Amplifier User Manual

Page 58

Advertising
background image

58

Rockwell Automation Publication 23P-UM001D-EN-P - July 2012

Chapter 3 Gate Amplifier Installation and Wiring

Gate Interface to Rockwell Automation Power Modules

Rockwell Automation power modules 356405-Cxx, 356406-Cxx and 356407-
Cxx do not contain gate couplers. The gate couplers are contained in a separate
unit called the Gate Coupler Assembly. The basic interface configuration is
shown in

Figure 25

-

Connection to Rockwell Automation Power Modules

.

Cables appear in the tables following the illustration below.

Figure 25 - Connection to Rockwell Automation Power Modules

Table 12 - Round Style Connector Forward Gate Cables

Additional lengths can be found on drawing 97305100.

Table 13 - Round Style Connector Reverse Gate Cables

Additional lengths can be found on drawing 97305300.

Table 14 - Output of Gate Coupler Assembly to SCR Gate Cable

To view drawing, 97329100, (an increased length cable may be added in the
future, it will appear on the drawing when available.)

Gate Amplifier

FWD GATES

REV GATES

(Drawing 97305100)

(Drawing 97305300)

SD3K-CBLFWDPMxxx

SD3K-CBLREVPMxxx

Gate Coupler Assembly

SD3K-GATMDLHIGH

(9732017* to view drawing)

Gate Coupler Assembly

SD3K-GATMDLHIGH

(9732017* to view drawing)

(Drawing 97329101)

SD3K-CBLCPLR072

(Make as short as possible.

Do not route with power leads.)

(Drawing 97329101)

SD3K-CBLCPLR072

(Make as short as possible.

Do not route with power leads.)

Terminal Block

(Mounted on

power module)

Terminal Block

(Mounted on

power module)

Power

Modules

FWD

Module

REV

Module

Catalog Number

Length

SD3K-CBLFWDPM060

5 Feet

SD3K-CBLFWDPM120

10 Feet

SD3K-CBLFWDPM180

15 Feet

SD3K-CBLFWDPM240

20 Feet

Catalog Number

Length

SD3K-CBLREVPM060

5 Feet

SD3K-CBLREVPM120

10 Feet

SD3K-CBLREVPM180

15 Feet

SD3K-CBLREVPM240

20 Feet

Catalog Number

Description

SD3K-CBLCPLR072

The cable is a twisted pair wire with "box" connectors on one end that plug
onto the Gate Coupler Boards that are in the Gate Coupler Assembly. The
opposite ends are "pig-tails" for connecting the power module gate input
terminal blocks. Use a second set of this cable type for an S6R
configuration. (Cut to desired length, as short as possible.) Do not route
with power leads.

Advertising