Rockwell Automation Publication 23P-UM001D-EN-P - July 2012

Chapter 2 Stand Alone Regulator Installation, Wiring and Configuration

Power Module Thermal

Switch and Current

Transformer Wiring

Connector KPT31 is used for power module thermal switch monitoring and
current feedback via current transformer connections. Note that the thermal
monitor circuit includes a thermal switch on the field power module within the
SAR.

Figure 8 - Power Module Thermal Switch and Current Transformer Terminal Block

(KPT31)

Table 6 - Power Module Thermal Switch and Current Transformer Terminal

Specifications

Current Transformer Connections

Current transformer 1 (CT1) monitors the U phase, with the “+” output of CT1
connected to terminal 5 of KPT31 and the “-” output of CT1 connected to
terminal 6 of KPT31.

Current transformer 2 (CT2) monitors the W phase, with the “+” output of
CT2 connected to terminal 7 of KPT31 and the “-” output of CT2 connected to
terminal 8 of KPT31.

The “-” side of the CTs are connected together internally in the SAR.

Terminal Description

Wire Size Range

Recommended

Torque

Maximum

Minimum

1, 2, 3

Thermal Switch Monitor

(1)

(1) These terminals are jumpered by default. The jumper wires must remain in place if a power module thermal

switch is NOT connected.

2.5 mm

2

(12 AWG)

0.2 mm

2

(24 AWG)

0.5…0.6 N•m
(4.4…5.3 lb•in)

5, 6, 7, 8

Current Transformer Feedback

1A1

(C)

A1 1A2

(D)

A2

V1 U1 C1 D1

D C W V U

KPT21

KPT11

KPT31

PE

1 2 3 4 5 6 7 8

Power Module
Thermal Switch and
Current Transformer
(KPT31) Terminal
Block

Bottom View of SAR