Step 7: Installing the High
Power Fiber Optic Interface
Circuit Board

1. Connect the 10 conductor ribbon cable from P6 on the Main Control circuit

board to J17 on the High Power Fiber Optic Interface circuit board.

Important: Route the 10 conductor ribbon cable, connected to C1 on the back

of the Main Control circuit board, under the High Power fiber
Optic Interface circuit board.

2. Secure the High Power Fiber Optic Interface circuit board to the control

frame using five screws.

3. Carefully connect the fiber-optic cables to the fiber-optic sockets on the right

side of the circuit board.

Important: Minimum inside bend radius for fiber-optic cable is 25.4 mm (1

in.). Any bends with a shorter inside radius can permanently
damage the fiber-optic cable. Signal attenuation increases with
decreased inside bend radii.

!

ATTENTION: Hazard of permanent eye damage exists when using
optical transmission equipment. This product emits intense light and
invisible radiation. Do not look into fiber-optic ports or fiber-optic
cable connectors.

10-Position Ribbon Cable

Note: Main Control cassette not

shown for clarity only

Control Frame

=