Modes of operation, Powerup reset mode, The communication card has 3 modes of operation – Rockwell Automation 825-MDN Smart Motor Manager DeviceNet Communication Card User Manual User Manual

Page 17: Run mode

Advertising
background image

Publication 825-UM002A-EN-P - December 2000

Operation 3-3

Figure 3.1 DeviceNet Status Display

Contact the nearest Allen-Bradley sales office if a status code other than these listed is returned

Modes of Operation

The Communication Card has 3 modes of operation:

Powerup Reset mode

Run Mode

Error Mode

Powerup Reset Mode

During a powerup or reset, the Communication Card:

Sets the Module Communication Status field in the DeviceNet

Status Display to 00.

Performs powerup initialization. If initialization fails, the Current

Module Communication Status field in the DeviceNet Status

Display is set to 04. You must recycle power to recover from a

power-up initialization failure. Repeated failures may indicate a

faulty Communication Card or a faulty SMM.

Performs a duplicate node address check to verify that another

node is not assigned the same DeviceNet MAC_ID as the

Communication Card.

DeviceNet: 00:00:000

Module Communication Status

Previous Module Communication Status

Device Poll Request Counter

Status Code

Description

00

No DeviceNet Power or Initializing.

01

Device is on-line with duplicate MAC check complete. Device not
allocated to master.

02

Normal operating state. Device is allocated to a master.

03

I/O connection has timed out.

04

Unrecoverable fault.