Publication 825-UM002A-EN-P - December 2000

A-43

ODVA Drive Profile Fault and Warning Codes Supported,
Continued

ODVA Fault

Code (hex)

ODVA Fault

Indication

SMM

LCD Indication

Possible Causes

Corrective Action

49 hex

Trips/Hour Exceeded

START INHIB TRIP

1. Wait until a further start is permissible.

Release will be automatic

65 hex

Tripping Time Exceeded

START CONTR TRIP

1. Overloaded
2. Transport material jammed

3. Viscous material

1. Reduce load or raise max. starting time
2. Eliminate cause

3. Raise max. starting time

66 hex

Transducer

MCM NOT CONNECT

FAULT MCM

1. Cable SMM <-> MCM broken or

not connected

2. Fault in 825-SMM or 825-MCM

1. Check connections, test cable

2. Send 825-SMM or 825-MCM back for

repair

2250 hex

Short Circuit

SHORT CIRC PROT

1. Short circuit or earth fault in

motor or cable

2. Trip when motor switched on,

due to inrush current

3. Pickup threshold is < Ia

1. Repair damage

2. Increase trip delay to >0.1 s

3. Set pickup threshold to > Ia

4310 hex

Excess Motor
Temperature

PT100 #...WARNING
PT100 #...TRIP

PTC TRIP

1. Stator winding overheated
2. PT100/PT100 leads or PTC/PTC

leads shorted or broken

1. Wait for motor to cool
2. Check leads or switch off PTC

monitoring

8114 hex

Illegal FLC Setting

IE OUT OF RANGE

1. Rated current MCM does not

agree with SMM setting

2. Wrong MCM

3. Wrong setting

1. Check setting of “FULL LOAD CURR”

and MCM

2. Install a correct MCM
3. Change FULL LOAD CURR setting

8116 hex

Command Outside
Window

ERROR ACTUAL VAL