Instance Attributes, Continued

Attribute

ID

Access

Rule

Name (param. #)

Data
Type

Min/Max

Units

Default

Description

109

Get/Set

as_prot_ (#28)

BOOL

0…1

1=ON

1

Asymmetry-protection, on/off

110

Get/Set

as_tr_le (#29)

USINT

5…80

%

35

Asymmetry, trip level

111

Get/Set

as_tr_ti (#30)

USINT

10…250

0.1 s

25

Asymmetry, trip delay (1.0…25.0 s)

112

Get/Set

as_alarm (#32)

BOOL

0…1

0=OFF

0

Asymmetry warning, on/off

113

Get/Set

as_al_le (#33)

USINT

5…80

%

20

Asymmetry, warning level

114

Get/Set

ol_prot_ (#35)

BOOL

0…1

1=ON

1

Overcurrent/locked rotor trip, on/off

115

Get/Set

ol_tr_le (#36)

USINT

10…60

times
0.1*FLC

24

Overcurrent/locked rotor, trip level
(1.0…6.0 times FLC)

116

Get/Set

ol_tr_ti (#37)

USINT

1…50

0.1 s

5

Overcurrent/locked rotor, trip delay
(0.1…5.0 s)

117

Get/Set

ol_alarm (#39)

BOOL

0…1

0=OFF

0

Overcurrent/locked rotor warning on/off

118

Get/Set

ol_al_le (#40)

USINT

10…60

times
0.1*FLC

20

Overcurrent/locked rotor warning level
(1.0…6.0 times FLC)

119

Get/Set

ef_prot_ (#42)

BOOL

0…1

1=ON

1

Earth-fault protection, on/off

120

Get/Set

efh_prot (#43)

BOOL

0…1

1=ON

1

Earth-fault prot., (Holmgreen) on/off

121

Get/Set

efh_tr_l (#44)

USINT

10…100

% Current 50

Earth fault (Holmgreen), trip level

122

Get/Set

efh_tr_t (#45)

USINT

1…50

0.1 s

5

Earth fault (Holmgreen), trip delay
(0.1…5.0 s)

123

Get/Set

efs_prot (#47)

BOOL

0…1

0=OFF

0

Earth-fault protection (core balance), on/
off

124

Get/Set

efs_tr_l (#48)

UINT

5…50000

0.005 A

1000

Earth-fault (core balance), trip level

125

Get/Set

efs_tr_t (#49)

USINT

1…50

0.1 sec

5

Earth-fault (core balance), trip delay
(0.1…5.0 s)

126

Get/Set

efs_al__ (#51)

BOOL

0…1

0=OFF

0

Earth-fault (core balance), warning on/off

127

Get/Set

efs_al_l (#52)

UINT

5…50000

0.005 A

500

Earth-fault (core balance), warning level

128

Get/Set

sc_prot_ (#54)

BOOL

0…1

0=OFF

0

Short circuit protection, on/off

129

Get/Set

sc_tr_le (#55)

USINT

40…120

times
0.1*FLC

100

Short circuit, trip level (4.0…12.0 times
FLC)

130

Get/Set

sc_tr_ti (#56)

USINT

2…99

10 ms

5

Short circuit, trip delay (20…990 ms)

131

Get/Set

ul_prot_ (#58)

BOOL

0…1

0=OFF

0

Underload protection, on/off

132

Get/Set

ul_tr_le (#59)

USINT

25…100

% FLC

75

Underload, trip level

133

Get/Set

ul_tr_ti (#60)

USINT

1…60

seconds

10

Underload, trip delay

134

Get/Set

ul_del_t (#62)

USINT

0…240

seconds

0

Underload trip, start delay

135

Get/Set

ul_alarm (#63)

BOOL

0…1

0=OFF

0

Underload warning, on/off

Advertising