Specific instance attributes, continued – Rockwell Automation 825-MDN Smart Motor Manager DeviceNet Communication Card User Manual User Manual

Page 57

Advertising
background image

Publication 825-UM002A-EN-P - December 2000

A-35

Specific Instance Attributes, Continued

➊ Available with SMM version 3.11 (or higher) / 825-MDN version 6.001 (or higher) product combination only.

Attribute ID

Access

Rule

Name

(param. #)

Data
Type

Min/
Max

Default

Description

131

Get/Set

sp2_t_of (#104)

USINT

0…240

2

Off-delay of auxiliary relay #3

132

Get/Set

dis_fct2 (#107)

BOOL

0…1

0

Disable protection functions from Control Input #2 on/off

133

Get/Set

drs_tr_r (#117)

USINT

0…7

0

Phase reversal trip, relay assignment

134

Get/Set

pas_tr_r (#119)

USINT

0…7

0

Phase loss trip, relay assignment

135

Get/Set

pt_tr_re (#133)

USINT

0…4, 7

0

Pt100 #1…#6 trip, relay assignment

136

Get/Set

pt_al_re (#148)

USINT

1…4, 7

1

Pt100 #1…#6 warning, relay assignment

137

Get

sp_in_st (#20)

UINT

0…3

0

Status of Control inputs #1 and #2; bit 0=Input 1 status,
bit 8=Input 2 status; 0=OFF, 1=ON

138

Get/Set

re2_comm (#225)

BOOL

0…1 0

Aux

#2

relay

ON/OFF

command

139

Get/Set

re3_comm (#226)

BOOL

0…1

0

Aux #3 relay ON/OFF command

140

Get/Set

anout_us (#230)

USINT

0…2

0

Analog output configuration:
0=Thermal utilization (0-100%)
1=PT100max (0-200°C)
2=Motor current (0-200%)

141

Get/Set

rel_remt (#231)

BOOL

0…1

0

Control relays #2 and #3 via DeviceNet

142

Get/Set

Aux2 Pr FltState (#234)

BOOL

0…1

0

Aux relay #2 behavior on a trip condition.
0 = “Go to Value”, 1= “Hold Last State”

143

Get/Set

Aux2 Pr FltValue (#235)

BOOL

0…1

0

Go To Value setting for parameter #234.
0 = OFF, 1= On

144

Get/Set

Aux2 Dn FltState (#236) BOOL

0…1

0

Aux relay #2 behavior on a comm. fault condition. 0 =
“Go to Value”, 1= “Hold Last State”

145

Get/Set

Aux2 Dn FltValue (#237) BOOL

0…1

0

Go To Value setting for parameter #236.
0 = OFF, 1= On

146

Get/Set

Aux2 Dn IdlState (#238) BOOL

0…1

0

Aux relay #2 behavior on a comm. idle condition. 0 = “Go
to Value”, 1= “Hold Last State”

147

Get/Set

Aux2 Dn IdlValue (#239) BOOL

0…1

0

Go To Value setting for parameter #238.
0 = OFF, 1= On

148

Get/Set

Aux3 Pr FltState (#240)

BOOL

0…1

0

Aux relay #3 behavior on a trip condition.
0 = “Go to Value”, 1= “Hold Last State”

149

Get/Set

Aux3 Pr FltValue (#241)

BOOL

0…1

0

Go To Value setting for parameter #240.
0 = OFF, 1= On

150

Get/Set

Aux3 Dn FltState (#242) BOOL

0…1

0

Aux relay #3 behavior on a comm. fault condition. 0 =
“Go to Value”, 1= “Hold Last State”

151

Get/Set

Aux3 Dn FltValue (#243) BOOL

0…1

0

Go To Value setting for parameter #242. 0 = OFF, 1= On

152

Get/Set

Aux3 Dn IdlState (#244) BOOL

0…1

0

Aux relay #3 behavior on a comm. idle condition. 0 = “Go
to Value”, 1= “Hold Last State”

153

Get/Set

Aux3 Dn IdlValue (#245) BOOL

0…1

0

Go To Value setting for parameter #244. 0 = OFF, 1= On