Parameters supported, continued – Rockwell Automation 825-MDN Smart Motor Manager DeviceNet Communication Card User Manual User Manual

Page 42

Advertising
background image

Publication 825-UM002A-EN-P - December 2000

A-20

Parameters Supported, Continued

Parameter

No.

®=read-only

Parameter

Name

Object

Mapping

Description

Data
Type

Units

Min/Max

Default

123

PT100 #2 Trip

0x0F-123-1

PT100 #2 Trip, 0=OFF 1=ON

BOOL

0…1

0

124

#2 Trip Temp

0x0F-124-1

PT100 #2 Trip, Temperature

USINT

°

C 50…200

50

125

PT100 #3 Trip

0xB4-1-19

PT100 #3 Trip, 0=OFF 1=ON

BOOL

0…1

0

126

#3 Trip Temp

0x0F-126-1

PT100 #3 Trip, Temperature

USINT

°

C 50…200

50

127

PT100 #4 Trip

0x0F-127-1

PT100 #4 Trip, 0=OFF 1=ON

BOOL

0…1

0

128

#4 Trip Temp

0x0F-128-1

PT100 #4 Trip, Temperature

USINT

°

C 50…200

50

129

PT100 #5 Trip

0x0F-129-1

PT100 #5 Trip, 0=OFF 1=ON

BOOL

0…1

0

130

#5 Trip Temp

0x0F-130-1

PT100 #5 Trip, Temperature

USINT

°

C 50…200

50

131

PT100 #6 Trip

0x0F-131-1

PT100 #6 Trip, 0=OFF 1=ON

BOOL

0…1

0

132

#6 Trip Temp

0x0F-132-1

PT100 #6 Trip, Temperature

USINT

°

C 50…200

50

133

PT100 #1-6 Relay 0x29-1-135

PT100 #1...#6 Trip, Relay Assignment

USINT

0…4, 7

0

134

PT100 #1-6 Reset 0x0F-134-1

PT100 #1...#6 Trip Reset, 0=Manual

1=Automatic

BOOL

0…1

0

136

#1 Warning

0x0F-136-1

PT100 #1 Warning, 0=Off 1=On

BOOL

0…1

0

137

#1 Warning Temp 0x0F-137-1

PT100 #1 Warning, temperature

USINT

°

C 50…200

50

138

#2 Warning

0x0F-138-1

PT100 #2 Warning, 0=Off 1=On

BOOL

0…1

0

139

#2 Warning Temp 0x0F-139-1

PT100 #2 Warning, temperature

USINT

°

C 50…200

50

140

#3 Warning

0x0F-140-1

PT100 #3 Warning, 0=Off 1=On

BOOL

0…1

0

141

#3 Warning Temp 0x0F-141-1

PT100 #3 Warning, temperature

USINT

°

C 50…200

50

142

#4 Warning

0x0F-142-1

PT100 #4 Warning, 0=Off 1=On

BOOL

0…1

0

143

#4 Warning Temp 0x0F-143-1

PT100 #4 Warning Temperature

USINT

°

C 50…200

50

144

#5 Warning

0x0F-144-1

PT100 #5 Warning, 0=Off 1=On

BOOL

0…1

0

145

#5 Warning Temp 0x0F-145-1

PT100 #5 Warning, temperature

USINT

°

C 50…200

50

146

#6 Warning

0x0F-146-1

PT100 #6 Warning, 0=Off 1=On

BOOL

0…1

0

147

#6 Warning Temp 0x0F-147-1

PT100 #6 Warning, temperature

USINT

°

C 50…200

50

148

#1-6 Warning Rel 0x29-1-136

PT100 #1-#6 Warning Relay 1=alarm
2=Aux #1 3=Aux #2 4=Aux #3

7=None

USINT

1…4, 7

1

150

T amb in Image

0x0F-150-1

PT100 #7 Include Ambient Temperature
in Thermal Image, 0=OFF 1=ON

BOOL

0…1

0

151 ®

Device MAC ID

0x03-1-1

Device MAC ID

USINT

0…63

63

152 ®

Baud Rate

0x03-1-2

Communication Baud Rate 0=125kB

1=250kB 2=500kB

USINT

0…2

0

154

Trip Reset

0x29-1-12

Remote Trip Reset Via Communications
0=No Reset 1=Reset

BOOL

0…1

0

Advertising