Rockwell Automation 825-MDN Smart Motor Manager DeviceNet Communication Card User Manual User Manual

Page 28

Advertising
background image

Publication 825-UM002A-EN-P - December 2000

A-6

Instance100 Data (User Configurable Input Assembly)

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Parameter Value (Low byte) pointed to by 0X05-2-102.

1

Parameter Value (High byte) pointed to by 0X05-2-102.

2

Parameter Value (Low byte) pointed to by 0X05-2-103.

3

Parameter Value (High byte) pointed to by 0X05-2-103.

4

Parameter Value (Low byte) pointed to by 0X05-2-104.

5

Parameter Value (High byte) pointed to by 0X05-2-104.

6

Parameter Value (Low byte) pointed to by 0X05-2-105.

7

Parameter Value (High byte) pointed to by 0X05-2-105.

Instance 101: Average Current Overload (Input)

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Reserved Reserved Reserved Reserved Reserved Reserved Warning Faulted

1

Reserved

2

Average 3Ø Current (Low byte)

3

Average 3Ø Current (High byte)

Instance 102: Phase Current Overload (Input)

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Reserved Reserved Reserved Reserved Reserved Reserved Warning Faulted

1

Reserved

2

Current Phase L1 (low byte)

3

Current Phase L1 (high byte)

4

Current Phase L2 (low byte)

5

Current Phase L2 (high byte)

6

Current Phase L3 (low byte)

7

Current Phase L3 (high byte)

Instance 103: Current Overload (Input)

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Reserved Reserved Reserved Reserved Reserved Reserved Warning Faulted

1

% Thermal Capacity Used, TCU

2

Average 3Ø Current (Low byte)

3

Average 3Ø Current (High byte)

4

% Asymmetry

Advertising