➊ Available with SMM version 3.11 (or higher) / 825-MDN version 6.001 (or higher) product combination only.

Attribute ID

Access

Rule

Name

(param. #)

Data
Type

Min/

Max

Default

Description

100

Get/Set

rel_th_t (#24)

USINT

0, 7

0

Thermal trip, relay assignment

101

Get/Set

th_al_re (#27)

USINT

1…7

1

Thermal warning, relay assignment

102

Get/Set

as_tr_re (#31)

USINT

0…7

0

Asymmetry trip, relay assignment

103

Get/Set

as_al_re (#34)

USINT

1…7

1

Asymmetry warning, relay assignment

104

Get/Set

ol_tr_re (#38)

USINT

0…7

0

Overcurrent/locked rotor, trip relay

105

Get/Set

ol_al_re (#41)

USINT

1…7

1

Overcurrent/locked rotor, warning relay assignment

106

Get/Set

efh_tr_r (#46)

USINT

0…7

0

Earth-fault (Holmgreen), trip relay

107

Get/Set

efs_tr_r (#50)

USINT

0…7

0

Earth-fault (Core balance), trip relay assignment

108

Get/Set

efs_al_r (#53)

USINT

1…7

1

Earth-fault (Core balance), warning relay assignment

109

Get/Set

sc_tr_re (#57)

USINT

2, 7

2

Short circuit, trip relay assignment

110

Get/Set

ul_tr_re (#61)

USINT

0…7

0

Underload, trip relay assignment

111

Get/Set

ul_al_re (#64)

USINT

1…7

1

Underload, warning relay assignment

112

Get/Set

star/del (#65)

BOOL

0…1

0

Star-delta starting, on/off

113

Get

st_relai (#66)

USINT

5

5

Star-delta starting, star relay

114

Get

delta_re (#67)

USINT

6

6

Star-delta starting, delta relay

115

Get/Set

star_tim (#68)

BOOL

0…1

0

Star-delta starting, max. star time on/off

116

Get/Set

star_tmx (#69)

USINT

1…240

10

Star-delta starting, max. star time

117

Get/Set

st/h_rel (#75)

USINT

0…7

0

Maximum starts/h, relay assignment

118

Get/Set

st_ti_re (#78)

USINT

0…7

0

Starting time exceeded, relay assignment

119

Get/Set

arb/ruhe (#79)

BOOL

0…1

0

Main relay and warning relay connection: non-failsafe
(0), electrically held (1)

120

Get/Set

ptc_tr_r (#84)

USINT

0, 7

0

PTC trip, relay assignment

121

Get/Set

sp_in_#1 (#86)

BOOL

0…1

0

Control Input #1, on/off

122

Get/Set

spin1_tr (#87)

BOOL

0…1

0

Time delay of aux. Relay #2, on/off

123

Get/Set

sp1_t_on (#88)

USINT

0…240

1

On-delay of auxiliary relay #2

124

Get/Set

sp1_t_of (#89)

USINT

0…240

2

Off-delay of auxiliary relay #2

125

Get/Set

speed_sw (#90)

BOOL

0…1

0

Speed switch/stop indicator on/off

126

Get/Set

sp_sw_re (#91)

USINT

0…7

0

Speed switch/stop indicator, trip relay

127

Get/Set

dis_fct1 (#92)

BOOL

0…1

0

Disable protection functions from Control Input #1 on/off

128

Get/Set

sp_in_#2 (#101)

BOOL

0…1

0

Control Input #2, on/off

129

Get/Set

spin2_tr (#102)

BOOL

0…1

0

Time delay of aux. Relay #3, on/off

130

Get/Set

sp2_t_on (#103)

USINT

0…240

1

On-delay of auxiliary relay #3

Advertising