Parameters Supported, Continued

Parameter

No.

®=read-only

Parameter Name

Object

Mapping

Description

Data
Type

Units

Min/
Max

Default

77

Max. Start Time

0x2C-1-142

Maximum Starting Time

USINT

seconds

1…240 10

78

Starttime Exceed

0x29-1-118

Starting Time Exceeded, Relay Assignment USINT

0…7

0

79

Rel-con Mn/Wrn

0x29-1-119

Main / Warning Relay Connection.
Bit-string
0=Non-Fail-Safe 1=Fail Safe

WORD

0…195 128

80

Th Trip Reset

0x29-1-143

Thermal Trip Reset, 0=Manual
1=Automatic

BOOL

0…1

0

81

Th Reset Level

0x2C-1-144

Thermal Trip Reset at... % of Thermal
Utilization

USINT

%

10…10
0

50

82

Cool-Const Ratio

0x2C-1-145

Cooling Constant Ratio, Motor OFF / Motor
ON (1.0…5.0)

USINT

0.1

10…50 25

83

PTC Trip

0x0F-83-1

Thermal Protection PTC, 0=OFF 1=ON

BOOL

0…1

0

84

PTC Trip Relay

0x29-1-120

PTC Trip, Relay Assignment

USINT

0…7

0

85

PTC Trip Reset

0x0F-85-1

PTC Trip Reset, 0=Manual, 1=Automatic

BOOL

0…1

0

86

Control Input #1

0x29-1-121

Control Input #1, 0=OFF 1=ON

BOOL

0…1

0

87

Delay Aux Rel #2

0x29-1-122

Time Delay of Auxiliary Relay #2, 0=OFF
1=ON

BOOL

0…1

0

88

On Delay Aux #2

0x29-1-123

On Delay of Auxiliary Relay #2

USINT

seconds

0…240 1

89

Off Delay Aux #2

0x29-1-124

Off Delay of Auxiliary Relay #2

USINT

seconds

0…240 2

90

Speed Switch

0x29-1-125

Speed Switch / Stop Indicator, 0=OFF 1=ON BOOL

0…1

0

91 ®

Sp Switch Relay

0x29-1-126

Speed Switch / Stop Indicator, Trip Relay
Assignment (is the same as no. 38)

USINT

0…7

0

92

Disable Prot #1

0x29-1-127

Disable Protective Functions, 0=OFF
1=ON

BOOL

0…1

0

93

As Prot #1

0x2C-1-146

Asymmetry Protection, 0=Not Disable
1=Disable

BOOL

0…1

0

94

OC Prot #1

0x2C-1-147

Overcurrent / Locked-Rotor Protection,
0=Not Disable 1=Disable

BOOL

0…1

0

95

EF Prot #1

0x2C-1-148

Earth Fault Protection, 0=Not Disable
1=Disable

BOOL

0…1

0

96

SC Prot #1

0x2C-1-149

Short Circuit Protection, 0=Not Disable
1=Disable

BOOL

0…1

0

97

UL Prot #1

0x2C-1-150

Underload Protection, 0=Not Disable
1=Disable

BOOL

0…1

0

98

St Inhib Prot #1

0x2C-1-151

Limiting the Starts Per Hour, 0=Not Disable
1=Disable

BOOL

0…1

0

99

PTC Prot #1

0x0F-99-1

PTC Protection, 0=Not Disable 1=Disable

BOOL

0…1

0