Rockwell Automation 825-MDN Smart Motor Manager DeviceNet Communication Card User Manual User Manual

Page 32

Advertising
background image

Publication 825-UM002A-EN-P - December 2000

A-10

Instance 2 Attributes (Predefined Slave Polled I/O Message)

Attribute

ID

Access

Rule

Name

Data
Type

Value

1

Get

State

USINT

0=nonexistant
1=configuring
3=established
4=timed out

2

Get

Instance Type

USINT

1= Poll Message

3

Get

Transport Class Trigger

USINT

0x82 - Server, Transport
Class 2

4

Get

Produced Connection ID

UINT

10xxxxxx100
xxxxxx=node address

5

Get

Consumed Connection ID

UINT

10xxxxxx101
xxxxxx=node address

6

Get

Initial Comm Characteristics

USINT

0x21

7

Get

Produced Connection Size

UINT

0…8 Size of assembly
instance selected

8

Get

Consumed Connection Size

UINT

0…1 Size of assembly
instance selected

9

Get/Set

Expected Packet Rate

UINT

Set by Master (00)

12

Get/Set

Watchdog Action

USINT

0=transition to timed out
1=auto delete
2=auto reset

13

Get

Produced Connection Path
Length

UINT

0…6 depending on path
type

14

Get/Set

Produced Connection Path

Set by Master during
configuration

15

Get

Consumed Connection Path
Length

UINT

0…6 depending on path
type

16

Get/Set

Consumed Connection Path

Set by Master during
configuration

Advertising